Abstract
We present a model for dimensioning low temperature grids of uninsulated pipes providing heating and cooling. Based on topological information about the grid, soil properties, and heating and cooling demands of the connected consumers, the model calculates the diameters of the pipes in the grid as well as the required length of the ground heat exchangers (GHEs) supplying the grid. This integrated approach allows the estimation of the heat gains from the uninsulated grid pipes which in turn reduces the required length of the GHEs. The model, implemented in Python and referred to as pythermonet, is available as free and open-source software. For modeling borehole heat exchangers (BHEs), we provide the choice to use either a model based on the infinite cylinder source (ICS) or the finite line source (FLS) solution implemented in the open-source Python package pygfunction. The BHE sizing method is validated against EED where we find a maximum deviation of 7.6% when using the ICS model and 1.3% when using the FLS model. Several grid topologies are simulated, and we estimate that the distribution pipes may supply 27–37% of the total demand.
| Original language | English |
|---|---|
| Journal | Science and Technology for the Built Environment |
| Volume | 31 |
| Issue number | 8 |
| Pages (from-to) | 879–888 |
| Number of pages | 10 |
| ISSN | 2374-4731 |
| DOIs | |
| Publication status | Published - 2025 |
Keywords
- construction, environment and energy
Fingerprint
Dive into the research topics of 'An integrated design model for ambient temperature district heating and cooling networks'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver